2 Instructions
2-162
CP1E CPU Unit Instructions Reference Manual(W483)
+B/+BL
Applicable Program Areas
Operands
Operand Specifications
Flags
Instruction Mnemonic Variations
Function
code
Function
BCD ADD WITHOUT CARRY +B @+B 404
Adds 4-digit (single-word) BCD data and/or con-
stants.
DOUBLE BCD ADD WITHOUT
CARRY
+BL @+BL 405
Adds 8-digit (double-word) BCD data and/or con-
stants.
Symbol
+B +BL
Area Step program areas Subroutines Interrupt tasks
Usage OK OK OK
Operand Description
Data type Size
+B +BL +B +BL
Au
+B: Augend word
+BL: First augend word
WORD DWORD 1 2
Ad
+B: Addend word
+BL: First addend word
WORD DWORD 1 2
R
+B: Result word
+BL: First result word
WORD DWORD 1 2
Area
Word addresses Indirect DM addresses
Constants CF Pulse bits TR bits
CIO WR HR AR T C DM @DM *DM
Au, Ad
OK OK OK OK OK OK OK OK OK
OK
--- --- ---
R ---
Name Label
Operation
+B +BL
Error Flag P_ER ON when Au is not BCD.
ON when Ad is not BCD.
OFF in all other cases.
ON when Au, Au +1 is not BCD.
ON when Ad, Ad +1 is not BCD.
OFF in all other cases.
Equals Flag P_EQ ON when the result is 0.
OFF in all other cases.
ON when the result is 0.
OFF in all other cases.
Carry Flag P_CY ON when the addition results in a carry.
OFF in all other cases.
ON when the addition results in a carry.
OFF in all other cases.
+B(404)
R
Au
Ad
Au: Augend word
Ad: Addend word
R: Result word
+BL(405)
R
Au
Ad
Au: 1st augend word
Ad: 1st addend word
R: 1st result word