Section 2-4
[Setting the rear switches]
CTS
0V
External
I/O port selection
selector switch
Set this to “RS-232C”.
Unit #
DIP SW1
Set SW1-1 to SW1-5 to “OFF”
“0”
.
S
nchronization
selector switch
Set this to “Internal”.
Baud rate
DIP SW2-1 to SW2-4
Set these switches to “1010” to select 9600 bps.
Set these switches to “0010” to select 19200 bps.
1-to-1/1-to-N selection
DIP SW2-6
Set SW2-6 to “0”
1-to-N
.
Instruction level
DIP SW2-7, SW2-8
Set these switches to “1”.
Levels 1, 2, and 3 are enabled.
CTS selection
selector switch
Set this alwa
sto“0V”
ON
.
I/O port
RS-422A
RS-232C
Synchronization
Internal
External
Termination
resistance
OFF
ON