Omron NT-series Programmable Terminal V022-E3-1 Bedienungsanleitung Seite 104

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 318
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 103
Automatic Reset
Data Bit Length
Stop Bit Length
ON
7bits
Parity Bit
Flow Control
2bits
Odd
XON/XOFF
[ MEMORY SWITCH MENU (2/2) ]
RS-232C Speed 19200bps
EXIT
SAVE
EXIT
PREV.
PAGE
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode

Section 3-6
The setting changes when each
of the touch switches is pressed
are indicated below.
“Automatic Reset” Alternates between “OFF” and “ON”
“Data Bit Length” Alternates between “8 bits and “7 bits”
“Stop Bit Length” Alternates between “2 bits” and “1 bit”
“Parity Bit” Changes among None”, “Even” and “Odd”
“Flow Control” Changes among None”, “RS/CS”
and “XON/XOFF”
“RS-232C Speed” Changes among “2400 bps”, “4800 bps”,
“9600 bps” and “19200 bps
To set and quit the menu, press the [SAVE EXIT] touch switch. To quit without set-
ting, press [EXIT].
4-6-5 Selecting the Automatic Reset Function
The “Automatic Reset” memory switch in MEMORY SWITCH MENU 2 selects
whether or not operation is automatically restarted after the occurrence of a com-
munication error.
The factory setting for the automatic reset function is “OFF”.
Select whether the automatic reset function is off or on by operation from the Sys-
tem Menu as described below.
Select “Maintenance Mode”.