Communicating between OMRON PLCs Section 8-6
8-6-4 Writing Programs
Programs incorporating the SEND(090), RECV(098), and CMND(490)
instructions are generally created using the Communications Port Enabled
Flag and the Communications Port Error Flag as input conditions. CS/CJ-
series CPU Units have eight communications ports. Only one instruction can
be executed at any given port at one time, however, so the program must not
overlap the use of any of the ports. A program example is provided below.
File memory 22 01 FILE NAME READ Reads file memory data.
22 02 SINGLE FILE READ Reads a specified length of file data
from a specified position within a single
file.
22 03 SINGLE FILE WRITE Writes a specified length of file data
from a specified position within a single
file.
22 04 FILE MEMORY FORMAT Formats (initializes) the file memory.
22 05 FILE DELETE Deletes specified files stored in the file
memory.
22 07 FILE COPY Copies files from one file memory to
another file memory in the same sys-
tem.
22 08 FILE NAME CHANGE Changes a file name.
22 0A MEMORY AREA–FILE TRANSFER Transfers or compares data between the
I/O memory area and the file memory.
22 0B PARAMETER AREA–FILE TRANSFER Transfers or compares data between the
parameter area and the file memory.
22 0C PROGRAM AREA–FILE TRANSFER Transfers or compares data between the
UM (User Memory) area and the file
memory.
22 15 CREATE/DELETE DIRECTORY Creates or deletes a directory.
Debugging 23 01 FORCED SET/RESET Force-sets or force-resets bits, or
releases force-set status.
23 02 FORCED SET/RESET CANCEL Cancels all bits that have been force-set
or force-reset.
Usage Command
code
Name Function
MR SR
There are eight communications ports, so up to eight
communications instructions can be executed at a time. The
number of messages that can be sent or received with a
single CPU Bus Unit service, though, is not more than two
each for the CPU Unit to the EtherNet/IP Unit and for the
EtherNet/IP Unit to the CPU Unit.
Communications port
EtherNet/IP Unit
CPU Unit
Instruction 1
Instruction 2
Instruction 3
Instruction 4
Instruction 5
Instruction 6
Instruction 7
Instruction 8
Seitenansicht 251
1 2 ... 247 248 249 250 251 252 253 254 255 256 257 ... 463 464

Kommentare zu diesen Handbüchern

Lynwood 14 Mar 2024 | 16:50:43

How To Create An Awesome Instagram Video About Pornstars On Adultwork British Porn Stars Xxx (Https://Qooh.Me)